Mitsubishi Electric
Mitsubishi Electric Ecodan Multi PXZ outdoor unit (air-to-air + air-to-water)
Šifra modela: PXZ-4F75VG
Šifra modela: PXZ-5F85VG
Osnovne informacije
- Proizvođač
- Mitsubishi-electric
- Šifra modela
- PXZ-4F75VG
Tehnički podaci
| Općenito | |
|---|---|
| Brand | Mitsubishi Electric |
| Model vanjske jedinice | PXZ-4F75VG |
| Općenito | |
|---|---|
| Brand | Mitsubishi Electric |
| Model vanjske jedinice | PXZ-5F85VG |
Izvor: podaci proizvođača i ovlaštenih distributera; energetski razredi, SEER i SCOP provjereni u EU bazi energetskih oznaka (EPREL) gdje je dostupno.
The Mitsubishi Electric Ecodan Multi PXZ is an outdoor unit that provides air heating and cooling using domestic and commercial air-to-air indoor units, as well as water heating and domestic hot water preparation via an Ecodan air-to-water indoor unit. The PXZ-4F75VG can be connected to 1–3 air-to-air units and 1 air-to-water unit, while the PXZ-5F85VG can be connected to 1–4 air-to-air units and 1 air-to-water unit.

Key benefits
How it works
The operating mode adapts to the season.


Technical data
| Refrigerant | R32, pre-filled with 2.4 kg |
| Power supply | 230 V / 1 phase / 50 Hz, 25 A fuse |
| Operating range | air-to-air heating −20 to +24 °C, cooling −10 to +46 °C; air-to-water heating −20 to +24 °C, DHW −20 to +35 °C |
| Max. water output | 55 °C |
| Model | Air-to-air cooling kW | Air-to-air heating kW | SEER / SCOP (class) | Air-to-water A7/W35 kW (COP) | A7/W55 kW (COP) | A2/W35 kW (COP) | Heating at 35 °C | Heating at 55 °C | DHW (L profile) | Sound power level ZV dB(A) | Dimensions, weight | ZZ + ZV units | Max. length / height |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| PXZ-4F75VG | 7.2 (3.7–8.8) | 8.6 (3.4–10.7) | 8.1 A++ / 4.1 A+ | 7.5 (4.17) | 7.5 (2.46) | 6.8 (2.80) | A++ 154 % · SCOP 3.92 | A+ 113 % · SCOP 2.91 | A+ 130 % | 67 | 710 × 840 × 330 mm, 59 kg | 1–3 + 1 | 60 / 20 m |
| PXZ-5F85VG | 8.3 (3.7–9.2) | 9.3 (3.4–11.6) | 8.5 A+++ / 4.7 A++ | 8.5 (4.34) | 8.5 (2.61) | 7.8 (3.00) | A++ 157 % · SCOP 4.00 | A+ 111 % · SCOP 2.86 | A+ 135 % | 64 | 796 × 950 × 330 mm, 62 kg | 1–4 + 1 | 70 / 20 m |
Source: Deltron ME catalogue, p. 12–13; ME Air to Water Catalogue 2026, p. 35–36. ZZ = air-to-air, ZV = air-to-water.
Compatible indoor units (Deltron catalogue, p. 13)
Wall-mounted MSZ-RW, MSZ-LN, MSZ-EF, MSZ-AP, MSZ-AY, MSZ-BT; floor-standing MFZ-KT; ducted SEZ-M and PEAD-M; ceiling-mounted PCA-M (4F only); Ecodan hydrobox ERSD-VM2E and ERST17D/20D/30D-VM2E tanks. MSZ-AP71VG and SEZ-M71DA only with 5F85VG.
Comparison of models in the series
- The 5F85VG has higher capacity, more connections (5) and better air-to-air SEER/SCOP (8.5 / 4.7) than the 4F75VG (8.1 / 4.1).
- The 5F85VG is quieter (air-to-water sound power level 64 dB(A) compared to 67 dB(A)), but has a larger enclosure.
Comparison with other series
| Series | Refrigerant | Capacity / power supply | Max. output | Heating up to | Cooling | Indoor unit |
|---|---|---|---|---|---|---|
| Eco Inverter (SUZ) | R32 | 4–10 kW, 1 phase | 60 °C | −25 °C | +10…+46 °C | hydrobox or 170/200/300 L tank |
| Power Inverter (PUZ) | R32 | 8–14 kW, 1 or 3 phases | 68 °C | −25 °C | +10…+52 °C | hydrobox or 200/300 L tank |
| Flash Injection (PUZ-SHWM) | R32 | 8–14 kW, 1 or 3 phases | 70 °C | −30 °C | +10…+52 °C | hydrobox or 200/300 L tank |
| Power Inverter R410A (PUHZ-SW120) | R410A | 12 kW, 1 phase | 60 °C | −20 °C | −15…+46 °C | hydrobox or 200 L tank |
| Flash Injection R410A (PUHZ-SHW) | R410A | 8 / 11.2 / 23 kW, 3 phases | 60 °C | −28 °C (230: −25 °C) | −15…+46 °C | hydrobox |
| Ecodan Multi (PXZ) | R32 | 1 outdoor unit for air-to-air + air-to-water | 55 °C | −20 °C | −10…+46 °C | Ecodan hydrobox/tank (D) |
| Ecodan Multi Light | R32 | PXZ-5F85VG + tank | 55 °C (65 °C with heater) | −20 °C | −10…+46 °C | 200 L tank (stainless steel) |
Values from the Deltron ME catalogue (May 2026) and the ME Air to Water Catalogue 2026. Heating up to = guaranteed operating heating range (outdoor temperature).
What's included
PXZ outdoor unit. The price is for the outdoor unit only; air-to-air indoor units and Ecodan air-to-water indoor units are ordered separately.
Variant designations
- PXZ-4F75VG: outdoor unit (up to 3 air-to-air + 1 air-to-water)
- PXZ-5F85VG: outdoor unit (up to 4 air-to-air + 1 air-to-water)